We are currently seeking information for Lightning Arrestors as per the attached technical specifications. This is an urgent request for information. Please review the requirements in the attachment carefully.
Key details:
Product: Lightning Arrestors
Quantity: 255 units of different types based on the attachment (details in the table) based on the attachment (details in the table)
Technical Specifications:
Limiter Type: SM/SH
Nominal Network Voltage: 110kV/220kV/400kV
The Highest Operating Voltage: 420kV/245kV/123kV
Continuous Working Voltage: >=77kV/>=154kV/>=267kV
Nominal Voltage: >=96kV/>=192kV/>=336kV
Nominal Discharge Current: SH >= 20 kAp, SM >= 10 kAp
Rated Repeated Load: SH: Qrs >= 2.4 C, SM: Qrs >= 1.6 C
Nominal Thermal Energy: SH: Wth >= 10 kJ/kV, SM: Wth >= 7 kJ/kV
Resistance to Long-term Current Surges: SH >= 2 kA, SM >= 1 kA
Rated Short Circuit Current: >=40kA, >=50kA, >=63kA
Maximum Permissible Mechanical Load: Minimum SSL Value
Ice Layer Thickness: 10mm, 20mm
Level of Contamination: Class d - Heavy, class e - Very Heavy
Required Operating Position: Vertical - installation on a supporting structure, inverted - installation in a suspended position
Implemented Functions of the Operation Counter: Operation registration (counting), leakage current indicator, monitoring and recording of operation
Quote Deadline: Please provide the required information by the 23rd