Exceeding these loss values and the partial discharge (PD) level will result in contractual penalties as per the agreement.
Load Losses (kW)
For 25 MVA: 140
For 31.5 MVA: 150
For 40 MVA: 185
Partial Discharge Level: Less then 150 PC
Partial Discharge Level of HV and HV-LV Bushing Insulators: Less then 10 PC
Required Sound Power Level (dB(A))
For 25 MVA: 76 (ONAN); 79 (ONAF)
For 31.5 MVA: 77 (ONAN); 80 (ONAF)
For 40 MVA: 79 (ONAN); 82 (ONAF) Measurement required according to the standard at rated voltage and rated current.
We require the following quantities and specifications for each transformer type:
25 MVA:
110/15: 112 units
110/20: 4 units
31.5 MVA:
110/15: 4 units
110/20: 2 units
40 MVA:
110/15: 5 units
25/16/16 MVA:
110/15/6: 1 unit
31.5/6.5/25 MVA:
110/30/15: 1 unit
Additionally, could you please provide information regarding your typical lead time for the manufacturing and delivery of these products?
The deadline for submitting the quote is November 9, 2024. The full technical specification is attached for your reference.